The HMP60, manufactured by Vaisala, probe measures temperature for the range of -40° to 60°C, and relative humidity for the range of 0 to 100% RH. It is suitable for long-term, unattended monitoring, and is compatible with all Campbell Scientific dataloggers.
Read MoreThe HMP60 uses the INTERCAP capacitive RH chip. This chip is field-replaceable, which eliminates the downtime typically required for the recalibration process.
Supply Voltage | 5 to 28 Vdc (typically powered by datalogger’s 12 V supply) |
Current Consumption |
|
Filter Description | 0.2 µm Teflon membrane |
Settling Time | 1 s |
Housing Classification | IP65 |
Housing Material | AISI 316 stainless steel |
Filter Cap Material | Chrome-coated ABS plastic |
Field-Replaceable Chip or Recalibrate | Field-replaceable chip (RH only) |
Sensor Diameter | 1.2 cm (0.5 in.) |
Filter Diameter | 1.2 cm (0.5 in.) |
Length | 7.1 cm (2.8 in.) |
Weight | 0.05 kg (0.1 lb) with 1.83 m (6 ft) cable |
Relative Humidity |
|
Sensing Element | Vaisala’s INTERCAP capacitive chip |
Measurement Range | 0 to 100% RH (non-condensing) |
Typical Accuracy at -40° to 0°C |
|
Typical Accuracy at 0° to 40°C |
|
Typical Accuracy at 40° to 60°C |
|
Output Signal Range | 0 to 1 Vdc |
Air Temperature |
|
Sensing Element | 1000 ohm Platinum Resistance Thermometer (PRT) |
Measurement Range | -40° to +60°C |
Accuracy | ±0.6°C |
Output Signal Range | 0 to 1 Vdc |
Please note: The following shows notable compatibility information. It is not a comprehensive list of all compatible products.
Product | Compatible | Note |
---|---|---|
CR1000 (retired) | ||
CR1000X | ||
CR300 | ||
CR3000 (retired) | ||
CR310 | ||
CR350 | ||
CR6 | ||
CR800 (retired) | ||
CR850 (retired) |
When exposed to sunlight, the HMP60 must be housed in a 41303-5A, 41303-5B, or RAD06 6-plate naturally aspirated radiation shield. The 41303-5A and RAD06 attaches to a crossarm, mast, or user-supplied pipe with a 2.5 to 5.3 cm (1.0 to 2.1 in.) outer diameter. The 41303-5B attaches to a CM500-series pole or a user-supplied pole with a 5.1 cm (2.4 in.) outer diameter.
The RAD06 uses a double-louvered design that offers improved sensor protection from driving rain, snow, and insect intrusion, It also has lower self-heating in bright sunlight combined with higher temperatures (> 24°C [~75°F]) and low wind speeds (< 2 m s-1 [~4.5 mph]), giving a better measurement.