Limited Availability ›
This product has limited availability. Some accessories, replacement parts, or services may still be available when it is no longer available.
NL121 Ethernet Interface
Adds Ethernet Connectivity
Connect a CR1000 or CR3000 to an IP network
weather aplicaciones soportadas water aplicaciones soportadas energy aplicaciones soportadas gas flux and turbulence aplicaciones soportadas infrastructure aplicaciones soportadas soil aplicaciones soportadas

Overview

The NL121 is the easiest and lowest-cost way to add an Ethernet interface connection to your CR1000 or CR3000. This small device, about the size of a deck of cards, simply plugs onto the data logger’s peripheral port. Through the NL121, you can access the Internet capabilities of your data logger, such as PakBus, Modbus, and DNP3 over TCP, as well as web, email, file transfer, and cloud-based application clients. You can collect from and control your data logger over any standard IP network—within your office or across the Internet.

Benefits and Features

  • The easiest way to add Ethernet to a CR1000 or CR3000
  • Provides a native Ethernet connection, allowing the data logger to communicate directly using a variety of Internet protocols
  • Integrated protection for surge and ESD
  • Data-logger-controlled power management for low-power operation

Images

NL121
NL121
NL121
NL121 front view
NL121 back view
NL121 left view
NL121 right view
NL121 top view
NL121 bottom view
NL121 connected directly to the peripheral port of the CR1000 (sold separately)

3D/CAD Files:

Compatibility

Data Logger Requirements

A CR1000 or CR3000 datalogger using operating system version 28 or greater is required.

Specifications

Transmission Distance or Area Worldwide
Data Logger Interface 40-pin peripheral port on CR1000 or CR3000
Ethernet 10/100 Mbps, auto-detect 10BaseT/100Base-TX, full/half duplex, IEEE 802.3, auto MDI/MDI-X
Power Source 12 V from data logger 40-pin peripheral port
Power Consumption
  • 58 mA (typical)
  • 3 mA (Ethernet off)
Operating Temperature Range -40° to +70°C
Service Requirements Ethernet access
Dimensions 10.2 x 6.4 x 2.8 cm (4.0 x 2.5 x 1.1 in.)
Weight 66.62 g (2.35 oz)

Compliance

Application of Council Directive(s) 2004/108/EC Electromagnetic Compatibility Directive (EMC)
2011/65/EU The Restriction of Hazardous Substances Directive (RoHS2)
Product Standard EN 61326-1:2013 – Electrical Equipment for measurement, control and laboratory use (EMC requirements – for use in industrial locations)